How many computers can I connect to a 30mA RCD protected circuit?

The switch mode power supply in a computer will leak up to 3.5mA to earth. A Hager 30mA RCD will not trip at 15mA but will trip at a point above 15mA and below 30mA. We would suggest no more than 4 computers on the one RCD circuit in order to ensure that unwanted tripping of the RCD does not occur.

More.

I cant really gove you an answer,but what I can give you is a way to a solution, that is you have to find the anglde that you relate to or peaks your interest. A good paper is one that people get drawn into because it reaches them ln some way.As for me WW11 to me, I think of the holocaust and the effect it had on the survivors, their families and those who stood by and did nothing until it was too late.